68    HC900 Process & Safety Controller User and Installation Manual  Revision 6 
    21 April 2017 
Mount Racks 
Rack assembly information is given in Table 8. 
Table 8 – Mount Racks 
Mount the Rack in the 
enclosure as follows. 
  Using the diagrams 
below as a guide, mark 
the locations for rack 
mounting in the 
enclosure for the top 
holes in the rack. 
 
(See CAUTION and 
Note at right.) 
  Drill and tap for # 10 (or 
M4) screws. 
  Start the mounting 
screws (supplied by the 
user) in the drilled 
holes. 
  Hang the Rack on the 
screws at the top.  
  Mark the locations for 
the bottom screws. 
 
(See CAUTION at 
right.) 
  Drill and tap for # 10 (or 
M4) screws. 
 
  Remove the rack from 
the enclosure. 
 
For dimensions of the pattern for drilling holes, refer to the 
diagram below. 
 
When drilling holes, prevent metal 
flakes from falling into the rack, or onto any surface within 
the electrical cabinet. 
Note: Always mount racks as shown above.  That is, never 
mount vertically, or with backplane horizontal.