calibration.   
CAUTION 
Because Function Blocks are not processed and outputs are Frozen in this mode, 
inputs (that is, process values) can vary from the values that existed when the 
OFFLINE Mode was entered. 
In Controllers with firmware earlier than V 6.0, the controller will resume program 
execution with current available data when controller returns to RUN mode. 
In Controllers with firmware version 6.0 or greater, the controller’s memory will get re-
initialized, outputs will be de-energized and the controller will restart when changing 
from Offline to Run mode.  
Before entering the OFFLINE Mode:  
  KNOW all potential consequences of suspending control action.. 
  PLAN for all operator actions required to preclude adverse consequences while 
processing is suspended, and when resuming control processing. 
  EXECUTE prudent control actions (such as placing all control loop in the Manual 
Mode). 
Failure to comply with these instructions may result in product damage.