210 HC900 Process & Safety Controller User and Installation Manual Revision 6
21 April 2017
Approvals
CE Conformity
This product is in conformity with the protection requirements of the following European
Council Directives: 2006/95/EC, the Low Voltage Directive, and 2004/108/EC
, the EMC Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not
be assumed. EN61326: Electrical Equipment For Measurement, Control and Laboratory use.
EMC requirements.
ATEX
The apparatus fulfills the requirements for Group II, Category 3 equipment in accordance with
Directive 94/9/EC.
ABS Type Approval
Certificate of Design Assessment - No. 06-HS186538-4-PDA (June 2014.)
No. 06-BA766694-X (York Location)
No. BY1100081X (Pune Location)
HC900 control system is NOT to be used for direct propulsion, steering, navigation or safety
systems. The controller must be installed in a grounded metal enclosure and must not be
used in non-weather protected spaces. Each application is to be approved on a case by case
basis.
General Purpose
Safety
Compliant with EN61010-1, UL, UL 61010-1 2
nd
edition, CSA C22.2 No. 1010-1
Hazardous
(Classified) Location
Safety
FM Class I, Div. 2, Groups A, B, C, D
CSA Class I, Div. 2 Groups A, B, C, D
Class 1, Zone 2, IIC
Module Temperature
Classifications
Module Type
“T”
Rating
Module Type
“T”
Rating
Redundant CPU Rack
T6
Scanner 2
T4
Redundant PS Ext. Rack
T5
Analog Input (8 channels)
T6
8 Slot Redundant PS Ext. Rack
T6
Analog Input (16 chan)
T6
12 Slot Redundant PS Ext. Rack
T6
Analog Output (4 chan)
T4
4 I/O Slot Rack
T6
Analog Output (8 chan)
Analog Output (16 channel)
T4
T3C
8 I/O Slot Rack
T6
Digital Input, Contact type (16 chan)
T5
12 I/O Slot Rack
T6
Digital Input, 24 Vdc (16 chan)
T4
Power Supply (P01)
T4
Digital Input, 120/240 Vac (16 chan)
T3C@ Ta= 60 deg. C
T4 @ Ta = 40 deg. C
Digital Input 120/240VAC, 125VDC
(16 Channel)
T3@Ta=60 deg. C
T4@Ta=40 deg. C
Power Supply (P02)
T4
Digital Input Vdc (32 chan)
T3@Ta=60 deg. C
T4@Ta=40 deg. C
Power Supply (P24)
T4
Digital Output, Relay type (8 chan)
T5
Power Status Module (PSM)
T6
Digital Output, 24 Vdc, (16 chan)
T4
C30/C50/C70/C75 CPU
T4
Digital Output, 120/240 Vac (8 chan)
T4
Redundancy Switch Module (RSM)
T6
Digital Output Vdc (32 chan)
T6
Scanner 1
T4
Pulse/Frequency/Quadrature (4 chan)