Specifications
Table 8-42 Access actuator technical specifications
DC input: Terminal, with input voltage of 36–60 V DC
POE input: One POE port that complies with IEEE802.3at.
FE communication, 10/100M communications rate
One wireless communication port that complies with IEEE802.15.4,
mutual backup with FE communication
Two AI/DI ports, can connect to the fire alarm and exit button
One 12 V DC power output that controls magnetic locks, terminal
One DI input port for connecting to the door status switch
RS485 serial port
expansion
Two RS485 ports (one route) with the default communications rate of
9600 bit/s, physical port cascading supported (reserved function)
Two Wiegand interfaces, 12 V DC card reader operating power
output; two routes of card readers (non-fingerprint readers) can
operate at the same time.
Press the button for less than 1 second to start blinking.
Hold down the button for 1–5 seconds to search for a network and
start networking.
Hold down the button for more than 10 seconds to clear network
parameters.
Indicators
Table 8-43 Access actuator indicator description
Power input status
indicator
Steady on: The power
input is normal.
Off: There is no
power input.
Communication status
indicator
Off: The power is
abnormal or the
board program is
loading.