EasyManua.ls Logo

IAI ELECYLINDER EC-S13 - Troubleshooting with no Alarm Generated; Operation Failure

IAI ELECYLINDER EC-S13
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.3 Troubleshooting with no alarm generated
7-8
7. Troubleshooting
7.3 Troubleshooting with no alarm generated
Operation failure
[Condition 1] SV/ALM LEDs do not light up
No. Possible cause Confirmation/countermeasure
1 The specified power is not supplied. Make sure that normal voltage is secured and
wiring processing is correct.
Also, be sure to check for disconnection or
partial disconnection in connectors and
wiring.
For details, refer to "3.4/3.5 Wiring
connections".
2 The unit is switched to servo OFF with the
teaching tool.
Turn ON the servo with PC software or teaching
pendant.
3 Controller breakdown Replace the controller cover assembly.
For details, refer to " Controller
replacement (page 8-17 to 21 and 22)".
If the unit still does not recover,
contact IAI.
[Condition 2] SV/ALM LEDs light up red
No. Possible cause Confirmation/countermeasure
1 Alarm generated. Connect the teaching tool.
Upon checking the alarm code, resolve the
cause.
For details, refer to "7.4 Troubleshooting by
alarm groups".
2 The stop switch of the teaching pendant
is being pressed.
Release the stop switch.

Table of Contents