Parameter List
‑39‑
Parame
ter
Address Name Value Range Default Unit Change
Method
Page
F9‑11 0xF90B Automatic fault
reset interval
0.1s to 100.0s 1 s In real time "
F9‑11
"
on
page 244
F9‑12 0xF90C Input phase loss/
Contactor pickup
protection
Ones (position): Input phase
loss protection selection
0: Input phase loss detection
inhibited
1: Input phase loss detected
by software and hardware
2: Input phase loss detected
by software
3: Input phase loss detected
by hardware
Tens (position): Contactor
pickup/Fan fault protection
0: Inhibited
1: Enabled
11 ‑ In real time "
F9‑12
"
on
page 244
F9‑13 0xF90D Restart interval
upon fault reset
0.0s to 600.0s 10 s In real time "
F9‑13
"
on
page 245
F9‑14 0xF90E 1st fault type 0 to 99 0 ‑ Unchangea
ble
"
F9‑14
"
on
page 245
F9‑15 0xF90F 2nd fault type 0 to 99 0 ‑ Unchangea
ble
"
F9‑15
"
on
page 245
F9‑16 0xF910 3rd (latest) fault
type
0 to 99 0 ‑ Unchangea
ble
"
F9‑16
"
on
page 245
F9‑17 0xF911 Frequency upon
3rd (latest) fault
0 Hz to 65535 Hz 0 Hz Unchangea
ble
"
F9‑17
"
on
page 246
F9‑18 0xF912 Current upon 3rd
(latest) fault
0.0–6553.5 A 0 A Unchangea
ble
"
F9‑18
"
on
page 246
F9‑19 0xF913 Bus voltage upon
3rd (latest) fault
0.0 V to 6553.5 V 0 V Unchangea
ble
"
F9‑19
"
on
page 246
F9‑20 0xF914 Input terminal
state upon 3rd
(latest) fault
0 to 65535 0 ‑ Unchangea
ble
"
F9‑20
"
on
page 246
F9‑21 0xF915 Output terminal
state upon 3rd
(latest) fault
0 to 65535 0 ‑ Unchangea
ble
"
F9‑21
"
on
page 247
F9‑22 0xF916 AC drive state
upon 3rd (latest)
fault
0 to 65535 0 ‑ Unchangea
ble
"
F9‑22
"
on
page 247
F9‑23 0xF917 Power‑on time
upon 3rd (latest)
fault
0 to 65535 0 ‑ Unchangea
ble
"
F9‑23
"
on
page 247
F9‑24 0xF918 Running time
upon 3rd (latest)
fault
0.0–6553.5 0 ‑ Unchangea
ble
"
F9‑24
"
on
page 247