DC Power Grounding Requirements and Warning
An insulated grounding conductor that is idencal in size to the grounded and ungrounded branch
circuit supply conductors but is idenable by green and yellow stripes is installed as part of the branch
circuit that supplies the device. The grounding conductor is a separately derived system at the supply
transformer or motor generator set.
WARNING: When you install the device, the ground connecon must always be made
rst and disconnected last.
Waarschuwing Bij de installae van het toestel moet de aardverbinding aljd het eerste
worden gemaakt en het laatste worden losgemaakt.
Varoitus Laitea asenneaessa on maahan yhdistäminen aina tehtävä ensiksi ja
maadoituksen ir kytkeminen viimeiseksi.
Averssement Lors de l'installaon de l'appareil, la mise à la terre doit toujours être
connectée en premier et déconnectée en dernier.
Warnung Der Erdanschluß muß bei der Installaon der Einheit immer zuerst hergestellt
und zuletzt abgetrennt werden.
Avvertenza In fase di installazione dell'unità, eseguire sempre per primo il collegamento
a massa e disconneerlo per ulmo.
Advarsel Når enheten installeres, må jordledningen alld lkobles først og frakobles sist.
Aviso Ao instalar a unidade, a ligação à terra deverá ser sempre a primeira a ser ligada, e
a úlma a ser desligada.
¡Atención! Al instalar el equipo, conectar la erra la primera y desconectarla la úlma.
Varning! Vid installaon av enheten måste jordledningen alld anslutas först och
kopplas bort sist.
DC Power Wiring Sequence Warning
WARNING: Wire the DC power supply using the appropriate lugs. When connecng
power, the proper wiring sequence is ground to ground, +RTN to +RTN, then –48 V to –
168