Table 20: Site Electrical Wiring Guidelines
(Connued)
Site Wiring
Factor
Guidelines
Electromagnet
ic
compability
If your site is suscepble to problems with electromagnec compability (EMC), parcularly
from lightning or radio transmiers, seek expert advice.
Strong sources of electromagnec interference (EMI) can cause:
Destrucon of the signal drivers and receivers in the device,
Electrical hazards as a result of power surges conducted over the lines into the equipment.
Rack Requirements for an EX4600 Switch
EX4600 Switches are designed to be installed on four-post racks.
Rack requirements consist of:
Rack type
Mounng bracket hole spacing
Rack size and strength
Table 21 on page 52 provides the rack requirements and specicaons for the EX4600 Switch.
Table 21: Rack Requirements for the EX4600 Switch
Rack Requirement Guidelines
Rack type Use a four-post rack that provides bracket holes or hole paerns spaced at 1 U
(1.75 in. or 4.45 cm) increments and that meets the size and strength requirements to
support the weight.
A U is the standard rack unit dened in
Cabinets, Racks, Panels, and Associated
Equipment
(document number EIA-310–D) published by the Electronics Industry
Associaon.