Table 19: EX Series Switch Environmental Tolerances
(Connued)
Switch or
device
Environment Tolerance
Altude Relave Humidity Temperature Seismic
EX9251
The maximum
thermal
output is
1705 BTU/
hour (500 W).
No performance
degradaon up to
10,000
(3048 m)
Normal operaon
ensured in relave
humidity range of 5% to
90%, noncondensing
Normal operaon ensured
in temperature range of
32° F (0° C) to 104° F
(40° C)
Nonoperang storage
temperature in shipping
container: – 40° F (–
40° C) to 158° F (70° C)
Complies with
Telcordia
Technologies
Zone 4
earthquake
requirements
XRE200 No performance
degradaon up to
10,000 feet
(3048 meters)
Normal operaon
ensured in the relave
humidity range 10%
through 85%
(noncondensing)
Normal operaon ensured
in the temperature range
41° F (5° C) through
104° F (40° C)
Complies with
Zone 4
earthquake
requirements as
per GR-63, Issue
4.
NOTE: Install EX Series switches only in restricted areas, such as dedicated equipment rooms
and equipment closets, in accordance with Arcles 110– 16, 110– 17, and 110– 18 of the
Naonal Electrical Code, ANSI/NFPA 70.
General Site Guidelines
Ecient device operaon requires proper site planning and maintenance. It also requires proper layout
of the equipment, rack or cabinet, and wiring closet.
To plan and create an acceptable operang environment for your device and prevent environmentally
caused equipment failures:
Keep the area around the chassis free from dust and conducve material, such as metal akes.
Follow prescribed airow guidelines to ensure that the cooling system funcons properly. Ensure
that exhaust from other equipment does not blow into the intake vents of the device.