Table 54: AC Power Cord Specifications (continued)
Plug TypeElectrical SpecificationModel NumberCountry
BS89/13240 VAC, 50 Hz ACCBL-M-PWR-RA-UKUnited Kingdom
Figure 26: M120 AC Plug Types
North Amer ica
(L6-20P)
North Amer ica
NEMA
(L6-20)
Australia
(SAA/3)
g003187
Japan
(L6-20P)
China
(PSB-10)
Italy
(CEI 23-16/VII)
Europe
(CEE 7/7)
UK
(BS89/13)
NOTE: If you plan to operate a maximally configured AC-powered router, we
recommend that you provision at least 33 A @ 240 VAC (11 A per inlet) for
the system, or at least 11 A maximum @ 240 VAC for each power supply. Use
a facility circuit breaker rated for 20 A, 125/250 VAC minimum for each AC
power supply. Doing so enables you to operate the router in any configuration
without upgrading the power infrastructure.
In North America and Japan, use both inlets for 125 VAC.
CAUTION: Power cords and cables must not block access to router
components or drape where people could trip on them.
Related
Documentation
M120 AC Power Supply Description on page 72
Replacing an M120 AC Power Supply on page 239
Replacing an M120 AC Power Supply Cord on page 244
Connecting Power to an AC-Powered M120 Router on page 167
Electrical Specifications for the M120 AC Power Supply
Table 55 on page 96 lists the AC power supply electrical specifications.
95Copyright © 2018, Juniper Networks, Inc.