Figure 30: Installing the M120 Mounting Hardware for an Open-Frame Rack
Open-frame
rack
Large
mounting shelf
g003482
Related
Documentation
M120 Rack Mounting Requirements on page 83
M120 Site Preparation Checklist on page 81
Installation Safety Warnings for Juniper Networks Devices on page 322
Installing the Mounting Hardware for a Center-Mount Open-Frame Rack
If you are installing the router in a center-mount open-frame rack, you must first install
the large mounting shelf on the rack. The spacer bars are not needed for this mounting
option; however, you can leave them attached to the front-mounting flanges.
Table 66 on page 121 specifies the holes in which you insert screws to install the mounting
hardware in an open-frame rack (an X indicates a mounting hole location). The hole
distances are relative to one of the standard U divisions on the rack. For reference, the
bottom of all mounting shelves is at 0.04 in. (0.02 U) above a U division.
To install the large mounting shelf (see Figure 30 on page 123):
123Copyright © 2018, Juniper Networks, Inc.
Chapter 16: Installing the Mounting Hardware