Keyscan Inc. A Member of the Kaba Group CA150 Rev. B Installation Guide (07.15)
27
Figure 12 - Terminate Door Strike - Less than 500 mA - Fail Secure
12 VDC+
Com
Ensure all lock hardware
complies with federal,
state/provincial, and
municipal fire codes.
Ground
Lug
POWER
INOUT
-
+
-
+
DOOR
AUX.
N/C
(+)
COM
(-)
N/O
(+)
N/C
(+)
COM
(-)
N/O
(+)
RS-485
A
B
(+ 12 VDC)
CA150B
Control Board
Cut View
Door Strike Powered from CA150
must be less than 500 mA
12V DC
Power Supply
+
+
-
-
J9
J8
J9
J8
Set J8 & J9 to Powered
# 18 AWG
# 18 AWG Green
Red
Black
Black
Red
# 18 AWG
Door
Strike
or
PoE
+
-
KI-00331E-11-12
12V DC power
supply or PoE for
power to all devices
maximum 680 mA
Keyscan recommends that power supplies have back-up batteries.
DOOR
AUX.
N/C
(+)
COM
(-)
N/O
(+)
N/C
(+)
COM
(-)
N/O
(+)
CA150
Install diode at terminal
block on CA150.
Observe polarity.