Keyscan Inc. A Member of the Kaba Group CA150 Rev. B Installation Guide (07.15)
32
Figure 17 Terminate Input Wiring RTE - PIR & Push Button
Lens
NO
COM
PIR (Request To Exit)
NO = Normally Open
PIR
Motion Sensor RTE (Request to Exit)
½ second pulse
Determines the amount of time the
output relays will energize when
motion is detected.
RTE
Push Button
COM
NO
NO = Normally Open
“Two devices wired in
parallel to each other”
Note
If using supervision, it is only required on the device farthest from the
ACU terminal. Example shows supervision on RTE Push Button.
DOOR
RTE AUX1 AUX2
-
+
-
+
-
+
-
+
Cut View of CA150B
Non-supervised
Normally Open
S2.8 = OFF
S2.7 = OFF
Single end of line supervision
Normally Open
S2.8 = OFF
S2.7 = ON
3K
to RTE -
to RTE +
1K
COM
NO
Double end of line supervision
Normally Open
S2.8 = ON
S2.7 = ON
to RTE -
to RTE +
1K
COM
NO
KI-00336E-02-14
S2.7 and S2.8 set the
supervision type universally.
The jumper setting affects
the Door Input, RTE Input,
and AUX Inputs.
S2
RDR/SUPV. CONFIG.
ON
6
7
8
9
10
2
3
4
5
1