EasyManua.ls Logo

LEGRAND PDU - Page 194

LEGRAND PDU
505 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
June 2018
194 Legrand PDU User Guide
Event/context Default message when the event =
TRUE
Default message when the event
= FALSE
unavailable. available.
Overcurrent Protector > * >
Sensor > * > Above upper
critical threshold
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]' asserted
'above upper critical' at
[SENSORREADING]
[SENSORREADINGUNIT].
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]'
deasserted 'above upper critical' at
[SENSORREADING]
[SENSORREADINGUNIT].
Overcurrent Protector > * >
Sensor > * > Above upper
warning threshold
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]' asserted
'above upper warning' at
[SENSORREADING]
[SENSORREADINGUNIT].
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]'
deasserted 'above upper warning'
at [SENSORREADING]
[SENSORREADINGUNIT].
Overcurrent Protector > * >
Sensor > * > Below lower
warning threshold
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]' asserted
'below lower warning' at
[SENSORREADING]
[SENSORREADINGUNIT].
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]'
deasserted 'below lower warning' at
[SENSORREADING]
[SENSORREADINGUNIT].
Overcurrent Protector > * >
Sensor > * > Below lower
critical threshold
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]' asserted
'below lower critical' at
[SENSORREADING]
[SENSORREADINGUNIT].
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]'
deasserted 'below lower critical' at
[SENSORREADING]
[SENSORREADINGUNIT].
Overcurrent Protector > * >
Sensor > Trip > Open/Close
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]' is open.
Sensor '[OCPSENSOR]' on
overcurrent protector '[OCP]' is
closed.
PDU > Controller > * >
Communication failed
Communication with controller
'[CONTROLLER]' (board ID
[BOARDID]) failed.
Communication with controller
'[CONTROLLER]' (board ID
[BOARDID]) restored.
PDU > Controller > * >
Firmware update
Controller '[CONTROLLER]' with board
ID [BOARDID] has started firmware
update
Controller '[CONTROLLER]' with
board ID [BOARDID] has completed
firmware update
PDU > Controller > * >
Incompatible
Controller '[CONTROLLER]' with board
ID [BOARDID] is incompatible.
Controller '[CONTROLLER]' with
board ID [BOARDID] is no longer
incompatible.
PDU > Controller > * > OK Controller '[CONTROLLER]' with board
ID [BOARDID] is OK.
Controller '[CONTROLLER]' with
board ID [BOARDID] is no longer
OK.
PDU > Load Shedding >
Started
PX placed in Load Shedding Mode by
user '[USERNAME]' from host
'[USERIP]'.
PX removed from Load Shedding
Mode by user '[USERNAME]' from
host '[USERIP]'.
Server Monitoring > * > Error Error monitoring server
'[MONITOREDHOST]': [ERRORDESC]
Server Monitoring > * >
Monitored
Server '[MONITOREDHOST]' is now
being monitored.
Server '[MONITOREDHOST]' is no
longer being monitored.
Server Monitoring > * >
Unreachable
Server '[MONITOREDHOST]' is
unreachable.
Server '[MONITOREDHOST]' is
reachable.

Table of Contents