218 Legrand PDU User Guide
8. Select "Activate Load Shedding" from the Available Actions list.
A Note about Infinite Loop
You should avoid building an infinite loop when creating event rules.
The infinite loop refers to a condition where the Legrand PDU keeps busy because the action or one of the
actions taken for a certain event triggers an identical or similar event which will result in an action triggering
one more event.
Example 1
This example illustrates an event rule which continuously causes the Legrand PDU to send out email
messages.
Event selected Action included
Device > Sending SMTP message
failed
Send email
Example 2
This example illustrates an event rule which continuously causes the Legrand PDU to send out SMTP
messages when one of the selected events listed on the Device menu occurs. Note that <Any sub-event>
under the Device menu includes the event "Sending SMTP message failed."
Event selected Action included
Device > Any sub-event Send email