Legrand PDU User Guide 371
config:# sensor inletpole <n> <p> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the inlet whose pole sensors you want to configure. For a single-inlet PDU, <n> is
always 1.
<p> is the label of the inlet pole that you want to configure.
Pole Label
<p>
Current sensor Voltage sensor
1
L1
L1 L1 - L2
2
L2
L2 L2 - L3
3
L3
L3 L3 - L1
<sensor type> is one of the following sensor types:
Sensor type Description
current Current sensor
voltage Voltage sensor
activePower Active power sensor
apparentPower Apparent power sensor
powerFactor Power factor sensor
activeEnergy Active energy sensor
unbalancedCurrent Unbalanced load sensor
Note: If the requested sensor type is not supported, the "Sensor is not available" message is displayed.
<option> is one of the options: enable, disable or a numeric value.
Option Description
enable Enables the specified threshold for the specified
inlet pole sensor.
disable Disables the specified threshold for the specified
inlet pole sensor.
A numeric
value
Sets a value for the specified threshold of the
specified inlet pole sensor and enables this
threshold at the same time.