Application Manual CDA3000
5-13
5 Software functions
1
2
3
4
5
6
A
DE
EN
FR
Storing a user data set (UDS) (164-UDSWR)
Customer/user settings are stored in one of the four possible user data
sets.
The user data set is selected by way of parameter 164-UDSWR and then
the parameter settings in the RAM are stored as a complete user data
set.
Note: Parameter 150-SAVE only ever saves the active data set to
the current user data set.
Switching between UDS (165-UDSAC, 166-UDSSL)
A user data set can be activated by way of parameter 165-UDSAC. The
active user data set is displayed as the parameter value.
The control location for activation of a user data set is defined with param-
eter 166-UDSSL.
816-SCTL1 CDS2: Speed controller lag time
817-SCTF1 CDS2: Jitter filter time constant
818-SCGF0 Speed controller gain at frequency zero
_84 MD Motor data, section 5.5.13
840 -MOFNM Nominal pole flux
841-MOL_S Leakage inductance
842-MOR_S Stator resistance
843-MOR_R Rotor resistance
844-MONPP Number of pole pairs of motor
Auto-tuning parameters
Used in control
mode
VFC SFC FOR
Table 5.6 Parameters changed during auto-tuning