Application Manual CDA3000
5-25
5  Software functions
1
2
3
4
5
6
A
DE
EN
FR
8 KTEMP Current heat sink tem-
perature
< 15 kW: Temperatures > 100 °C in the power 
stage module correspond to temperatures > 85 °C 
on the heat sink and result in shut-off
>
 15 kW: Temperatures >86 °C result in shut-off, 
because temperature sensor directly on heat sink
200 °C
9 DTEMP Current interior temper-
ature
Interior temperatures > 85 °C result in shut-off
200 °C
10 DCV  DC-link voltage Referenced values dependent on device version
CDA32.xxx   500 V
CDA34.xxx   1000 V
500 V / 1000 V
11 VMOT Motor voltage Referenced values dependent on device version
CDA32.xxx   500 V
CDA34.xxx   1000 V
500 V / 1000 V
12 PS Apparent power 2*PN
13 PW Active power 2*PN
14 ACTT Current actual torque Control mode FOR: true actual frequency
Control mode SFC: estimated actual frequency
Open-loop control mode VFC: no display
Dependent on device, 
see table
15 AACTF Amount of current actual 
frequency
Clockwise (pos. value) and anti-clockwise (neg. 
value) are represented as amounts. 
Control mode FOR: true actual frequency
Control mode SFC: estimated actual frequency
Open-loop control mode VFC: display of reference 
frequency
FMAX1/2
16 AACTN Amount of current actual 
speed
Clockwise (pos. value) and anti-clockwise (neg. 
value) are represented as amounts. 
Control mode FOR: true actual speed
Control mode SFC: estimated actual speed
Open-loop control mode VFC: no display
nN
BUS KP/DM Function Effect/Notes Referenced value 10 V
Table 5.14 Settings for 200-FOSA0 analog output