2-10
Application Manual CDA3000
2 Inverter module CDA3000
ENPO X2-8 Power stage enable = High level
Switching level Low/High: <5 V / >18 V DC
I
max
at 24 V = 10 mA
R
IN
= 3 kW
Internal signal delay time
20µs
Terminal scan cycle = 1ms
PLC-compatible (IEC1131)
Digital outputs
OSD0 0 X2-15 Short-circuit proof
PLC-compatible (IEC1131)
I
max
= 50 mA
Internal signal delay time
250µs
Terminal scan cycle = 1ms
Protection against inductive load
High-side driver
OSD0 1 X2-16 Short-circuit proof with 24V supply from
inverter module
PLC-compatible (IEC1131)
I
max
50mA
Internal signal delay time
2µs
Terminal scan cycle = 1ms
No internal freewheeling diode; provide exter-
nal protection
High-side driver
Data output with reference coupling
1)
Relay output
OSD0 2 X2-18
X2-19
X2-20
Relay 48 V / 1 A AC,
changeover contact
Usage category AC1
Operating delay approx. 10 ms
Motor temperature monitor
PTC1/ 2 X3-1
X3-2
Measured voltage max. 12 V DC
Measuring range 100
- 15 k
Suitable for PTC to DIN 44082
Suitable for temperature sensor KTY84, yel-
low
Suitable for thermostatic circuit-breaker (Klixon)
Sampling time 5 ms
Des.
Ter-
minal
Specification Floating
Table 2.6 Specification of control terminals