A-20
Application Manual CDA3000
Appendix B Error messages
Error messages
If a fault occurs in operation it is indicated by a flash code from LED H1
(red) on the inverter module. The code indicates the type of error. If a
KP200 is connected the KP200 indicates the error type as an abbrevia-
tion.
Service Hotline If you need further assistance, our specialists at the LUST Service Center
will be glad to help.
Flash code of
red LED H1
KeyPad
DISPLAY
Response
no.
Explanation Cause/Remedy
1x
E-CPU 3 Error in CPU (processor)
Switch power off and back on again. If error reoccurs
notify LUST Service.
2x
E-OFF 1 Undervoltage shut-off
Check power supply. Also occurs briefly in response to
normal power-off.
3x
E-OC 2 Current overload shut-off
Short-circuit, ground fault: Check cabling of connections,
check motor coil, check neutral conductor and grounding
(see also section 3, Installation).
Device setup not correct: Check parameters of control
loops. Check ramp setting.
4x
E-OV 2 Voltage overload shut-off
Voltage overload from mains: Check mains voltage. Restart
device.
Voltage overload resulting from feedback from motor
(regenerative operation): Slow down braking ramps. If not
possible, use a braking resistor.
5x
E-OLM 2 Motor protection shut-off
Motor overloaded (after I x t monitoring): Slow down proc-
ess cycle rate if possible. Check motor dimensioning.
6x
E-OLI 2 Device protection shut-off
Device overloaded: Check dimensioning. Possibly use a
larger device.
7x
E-OTM 2 Motor temperature too high
Motor PTC correctly connected?:
Parameter MOPTC (type of motor PTC evaluation) correctly
set?
Motor overloaded? Allow motor to cool down. Check
dimensioning.
8x
E-OTI 2 Inverter overheating
Ambient temperature too high: Improve ventilation in
switch cabinet.
Load too high during driving/braking: Check dimensioning,
poss. use braking resistor.
Table A.3 Error messages