1 MULTIPLE CPU SYSTEM
1.1 Multiple CPU System
Application
setting
Scaling function Scaling enable/disable setting Enable/Disable Disable
Scaling upper limit value -32000 to -1, 1 to 32000
Scaling lower limit value -32000 to -1, 1 to 32000
Shift function Conversion value shift amount -32768 to 32767 0
Digital clipping
function
Digital clipping enable/disable
setting
Enable/Disable Disable
Warning output
function
(process alarm)
Warning output setting (Process
alarm)
Enable/Disable Disable
Process alarm upper upper limit
value
0 to 32767
Process alarm upper lower limit
value
0 to 32767
Process alarm lower upper limit
value
-32768 to 0
Process alarm lower lower limit
value
-32768 to 0
Warning output
function (rate
alarm)
Warning output function (Rate
alarm)
Enable/Disable Disable
Rate alarm detection cycle
setting
1 to 32000 times
Rate alarm upper limit value 0.1 to 3276.7%
Rate alarm lower limit value -3276.8 to 0.1%
Input signal
error detection
function
Input signal error detection
setting
Disable/Upper/lower limit detection/Lower limit detection/
Upper limit detection
Disable
Input signal error detection
setting value
0.0 to 25.0%
Input signal error detection
lower limit setting value
0.0 to 25.0%
Input signal error detection
upper limit setting value
0.0 to 25.0%
Input signal error detection auto
clear enable/disable setting
Enable/Disable Disable
Logging function
(Normal logging
function)
Logging enable/disable setting Enable/Disable Disable
Logging data points setting 0 to 900 200
Logging data setting Digital output value/digital operation value
Logging cycle setting value s: 20 to 32767
ms: 1 to 32767
s: 1 to 3600
Logging cycle unit setting s/ms/s
Level trigger condition setting Disable/Level trigger (Condition: Rise)/Level trigger
(Condition: Fall)/Level trigger (Condition: Rise and Fall)/
Process alarm (Upper limit warning)/Process alarm (Lower
limit warning)/Process alarm (Upper limit warning and
lower limit warning)
Logging points after trigger 1 to 90000
Trigger data 0 to 9999
Trigger setting value -32768 to 32767
Level judgment count setting
value
1
to
10 times
Logging loading enable/disable
setting
Enable/Disable
Logging read points setting
value
1 to 10000
Continuous logging cycle setting
value
1 to 1000 1
Inter-module
synchronization
function
Oversampling mode Enable/Disable Disable
Online module
change
Auto restore of offset/gain
setting with the module change
Enable/Disable Enable
Item
*1
Setting range
*2
Default value

Table of Contents