1 MULTIPLE CPU SYSTEM
1.1 Multiple CPU System
27
1
*1 Items that can be set will differ depending on the module used.
*2 Setting range will differ depending on the module used.
*3 Default values will differ depending on the module used.
■Analog output module
*1 Items that can be set will differ depending on the module used.
*2 Setting range will differ depending on the module used.
*3 Default values will differ depending on the module used.
Interrupt
setting
Condition target setting Disable/Error flag/Warning output flag (Process alarm)/
Warning output flag (Rate alarm)/Input signal error
detection flag/A/D conversion completed/Logging hold flag/
Logging read/Continuous logging data storage
Disable
Condition target channel setting All CH specification/CH1/CH2/CH3/CH4/CH5/CH6/CH7/
CH8/CH9/CH10/CH11/CH12/CH13/CH14/CH15/CH16
All CH specification
Interrupt factor transaction setting Interrupt reissue requests/No Interrupt reissue requests Interrupt reissue requests
Interrupt pointer I0 to I15
Item
*1
Setting range
*2
Default value
Basic
setting
Range switching
function
Output range setting 4 to 20mA/0 to 20mA/1 to 5V/0 to 5V/-10V to 10V/-12V to
12V/4 to 20mA (Extension)/1 to 5V (Extension)/User range
setting (Voltage)/User range setting (Current)/User range
setting 3/User range setting 2/User range setting 1
*3
Operation mode
setting function
Operation mode setting Normal mode(D/A conversion process)/Offset/gain setting
mode
Normal mode(D/A
conversion process)
Output mode setting Normal output mode/Wave output mode Normal output mode
Output mode
setting function
Analog output HOLD/CLEAR
setting
CLEAR/HOLD CLEAR
D/A conversion
enable/disable
function
D/A conversion enable/disable
setting
D/A conversion enable/D/A conversion disable D/A conversion disable
Application
setting
Scaling setting Scaling enable/disable setting Enable/Disable Disable
Scaling upper limit value -32000 to -1, 1 to 32000
Scaling lower limit value -32000 to -1, 1 to 32000
Shift function Input value shift amount -32768 to 32767 0
Warning output
function
Warning output setting Enable/Disable Disable
Warning output upper limit value 1 to 32767
Warning lower upper limit value -32768 to -1
Rate control
function
Rate control enable/disable
setting
Enable/Disable Disable
Increase digital limit value 0 to 64000
Decrease digital limit value 0 to 64000
Inter-module
synchronization
function
Output selection during
synchronous error
Inter-module synchronization continue/Inter-module
synchronization stop
Inter-module
synchronization continue
Online module
change
Auto restore of Offset/gain
setting with the module change
Enable/Disable Enable
CPU error output mode setting Clear/Hold Clear
Interrupt
setting
Condition target setting Disable/Error flag/Warning output flag/Disconnection
detection flag/External power supply READY flag/External
power supply READY flag (CH1_CH8)/External power
supply READY flag (CH9_CH16)
Disable
Condition target channel setting All CH specification/CH1/CH2/CH3/CH4/CH5/CH6/CH7/
CH8/CH9/CH10/CH11/CH12/CH13/CH14/CH15/CH16
All CH specification
Interrupt factor transaction setting Interrupt reissue request/No Interrupt reissue request Interrupt reissue request
Interrupt pointer I0 to I15
Item
*1
Setting range
*2
Default value