PARISON CONTROLLER
moog
66 MAN145-UM-D01A-EN Moog Italiana srl - Bergamo
4.6.1 Check wirings.
To check the correct wiring:
Choose open loop calibration.
With the UP/DOWN keys verify the correct movement: if the UP key is pressed, the moving part has to
move up, if the DOWN key is pressed the moving part has to move down.
o If the movement is OK :
Check the bar graphs movement (yellow and blue). If bar graphs are moving in the same
direction, also the input is OK and it is possible to perform the calibration in close loop.
If the bar graphs are moving in opposite directions, reverse the input polarity by inverting
the parameter Inv. input in the head setup page
o If the movement is not OK :
Reverse the input polarity by inverting the parameter Inv. output in the head setup page
After this, the movement should be correct. If bar graphs are moving in the same
direction, also the input is OK and it is possible to perform the calibration in close loop.
If the bar graphs are moving in opposite directions, reverse the input polarity by inverting
the parameter Inv. input in the head setup page