9-32 Manual # 42-02-2223
Reference
LC23
KP Speed Res-
onance Decel
0-400 % 50
LC24
Speed at Reso-
nance Decel
1-50 ft/min 4
LC25 KP Speed High 0-400 - 100
LC30
Maximum
Torque
0-500 % 150
LC31
Reduced Maxi-
mum Torque
0-500 % 100
LC32
Low Speed
Torque Boost
Induction only 0-25.5 % 5.0
LC33
Auto Boost
Gain
Induction only- 0-2.50 - 0.00
LC34
Digital
Pretorque
--
-100.0-
100.0
%0.0
LC40
Acceleration
Torque
- - 0-12036 lb-ft 0
LC41 System Inertia
Geared
-
0-65501
lb-in
2
0
Gearless 0.0-1073.7
lb-yd
2
0.0
LC42 FFTC Filter
Off
250 Hz
125 Hz
63 Hz
31 Hz
16 Hz
8.0 Hz
4.0 Hz
2.0 Hz
1.0 Hz
0
1
2
3
4
5
6
7
8
9
-HzOff
LC43 FFTC Gain - - 0-200 % 0
LC44
Torque
Command
Filter
Off
2000 Hz
1000 Hz
500 Hz
250 Hz
125 Hz
63 Hz
31 Hz
0
1
2
3
4
5
6
7
- Hz 2000
LT Timer Parameters
LT01
Brake Release
Delay
- - 0.00-1.00 sec 0.05
0.00
LT02
Control Hold
Off
- - 0.00-1.00 sec 0.40
LT03
Speed Start
Delay
- - 0.00-3.00 sec 0.70
10.0
LT10
Brake Drop
Delay
- - 0.00-1.00 sec 0.10
0.00
Table 9.5 TORQMAX F5 Drive, v3.21 LCD Parameter Settings
Para. Name Setting Num Range Units Default
Field
Setting

Table of Contents