9-63
Magnetek Quattro AC Quick Reference
iControl AC
9
PRIORITY MESSAGE If disabled, user will not see priority messages.
Faults and alarms will not be displayed but
instead placed into fault history and active
fault lists with Fault LED on. Leave enabled.
None - disable
- enable
Enable Enable
ARB SELECT Anti-rollback select. When enabled, drive cal-
culates pretorque values when movement is
seen on shaft. See drive manual
None - enable
- disable
Disable Disable
C2 Logic inputs submenu
LOGIC INPUT 1
TB1(1)
Logic input #1: Drive prewired for CONTACT
CONFIRM
None contact cfirm,
ctr pwr sense,
drive enable,
extrn fault 1,
extrn fault 2,
extrn fault 3,
extrn /flt 4,
fault reset,
field enable,
low gain sel,
mech brk hold,
mech brk pick,
no function,
ospd test src,
pre-trq latch,
run,
run down,
run up,
s-curve sel 0,
s-curve sel 1,
ser2insp ena,
step ref b0,
step ref b1,
step ref b2,
step ref b3,
trq ramp
down, up/dwn
CON-
TACT
CFIRM
CON-
TACT
CFIRM
LOGIC INPUT 2
TB1(2)
Logic input #2: Drive prewired for CTR PWR
SENSE
None CTR
PWR
SENSE
CTR
PWR
SENSE
LOGIC INPUT 3
TB1(3)
Logic input #3 None NO
FUNC-
TION
NO
FUNC-
TION
LOGIC INPUT 4
TB1(4)
Logic input #4 None DRIVE
ENABLE
DRIVE
ENABLE
LOGIC INPUT 5
TB1(5)
Logic input #5 None RUN RUN
LOGIC INPUT 6
TB1(6)
Logic input #6 None UP/DWN NO
FUNC-
TION
LOGIC INPUT 7
TB1(7)
Logic input #7 None STEP
REF B0
NO
FUNC-
TION
LOGIC INPUT 8
TB1(8)
Logic input #8 None STEP
REF B1
NO
FUNC-
TION
LOGIC INPUT 9
TB1(9)
Logic input #9 None FAULT
RESET
FAULT
RESET
Table 10. Quattro PM Elevator Drive, iControl