9-74 Manual # 42-02-2223
Reference
Digital
Operator
Display
Parameter Description Unit
Setting
Range
Default
Setting
Factory
Setting
LF.78
Brake drop delay: Time motor will hold full current
and control after direction inputs drop.
sec 0.0-3.00 0.50 0.50 - 0.80
LF.79
Current hold time: Delay in turning off the drive
(Delay to turn OFF the motor current after the
direction is dropped and LF.78 has expired)
sec
0.300 -
3.000
0.300 0.30
Diagnostic Parameters (Read only)
LF.25 Estimated gear ratio 1
LF.80 Software version
LF.81 Software date MMDD.Y
LF.82 X2A-input state
see tables in
F5 Drive
Manual
LF.83 X2A-output state
LF.86 Operational mode
LF.87 Actual inverter load (100% = rated load) %
LF.88 Motor command speed rpm
LF.89 Actual motor speed rpm
LF.90 Actual elevator speed ft/m
LF.93 Phase current A
LF.94 Peak phase current A
LF.95 Actual DC voltage V
LF.96 Peak DC Voltage V
LF.97 Actual output frequency Hz
O.LF.98 Last error
US - Parameters
US. 1
Password: With different passwords, different
parameter groups can be accessed for advanced
programming.
- 0-9999 - -
US. 3
Load defaults. Select LoAd and press ENTER to
cause all LF parameters to be reset to drive default
values.
-LoAd - -
US. 4
Load configuration. Select LoAd and press ENTER
to load the configuration selected in US.10.
-LoAd - -
US.10
Select Configuration. User selection of drive mode.
I CLSd = Induction motor (closed loop)
I 9LSS = Induction motor (closed loop) gearless
P CLSd = Synchronous motor (closed loop)
P 9LSS = Synchronous motor (closed loop)gearless
Loaded using parameter US.04.
-
ICLSd
I 9LSS
P CLSd
P 9LSS
-
*
_________
* Parameters are motor/machine/job dependent.
** Recommended but field adjustable.
*** The value is automatically calculated from the motor data or other parameter values.
****Parameters apply to Drive Software Version 1.71 or greater)
Parameters for Drive Software Version (LF.80 = 1.61 or greater), Software date (LF.81 = 2801.9 or later)
Job #: Drive Serial #:
Prod. Order #: Test technician:
Drive Model #: Date:
Table 9.1 TORQMAX F5 Drive Parameters Quick Reference for iControl AC