FP0 HardwareI/O Allocation
7-4
Matsushita Electric Works (Europe) AG
7.3 Expansion I/O Unit
Up to three expansion I/O units can be added.
I/O numbers do not need to be set as I/O allocation is performed automatically by the
FP0 control unit when an expansion I/O unit is added.
The I/O allocation of expansion I/O unit is determined by the installation location.
I/O number
Type
First
expansion
Second
expansion
Third
expansion
E8RS Input: 4 points
X20 to X23
X40 to X43
X60 to X63
Output: 4 points
Y20 to Y23
Y40 to Y43
Y60 to Y63
E8X Input: 8 points
X20 to X27
X40 to X47
X60 to X67
E8YT/E8YP Output: 8 points
Y20 to Y27
Y40 to Y47
Y60 to Y67
E16RS/E16T/E16P Input: 8 points
X20 to X27
X40 to X47
X60 to X67
Output: 8 points
Y20 to Y27
Y40 to Y47
Y60 to Y67
E16X Input: 16 points
X20 to X2F
X40 to X4F
X60 to X6F
E16YT/E16YP Output: 16 points
Y20 to Y2F
Y40 to Y4F
Y60 to Y6F
E32T/E32P Input: 16 points
X20 to X2F
X40 to X4F
X60 to X6F
Output: 16 points
Y20 to Y2F
Y40 to Y4F
Y60 to Y6F
Third expansion
Second expansion
First expansion
Control unit