FP0 Hardware A.2 Tables of System Registers
A-7Matsushita Electric Works (Europe) AG
Address Name of system register
Default
value
Set value (parameter)
Time 30 Unused
setting
31 Wait time setting for
multi-frame communication
K2600
(6500ms)
K4 to K32760: 10ms to 81900ms
Use of default setting (K2600/ 6500ms) is
recommended.
set value × 2.5ms = Wait time setting for mul-
ti–frame communica-
tion (ms)
In FPWIN Pro or NPST–GR, enter
the time (a number divisible by 2.5).
In FP Programmer II, enter the set
value (equal to the time divided by
2.5).
32, 33 Unused With the FP0, values set with the program-
ming tool become invalid.
34 Constant value settings for
scan time
K0 K1 to K64 (2.5ms to 160ms): Scans once each
specified time interval.
K0: Normal scan
set value × 2.5ms = Constant value setting for
scan time (ms)
In FPWIN Pro or NPST–GR, enter
the time (a number divisible by 2.5).
In FP Programmer II, enter the set
value (equal to the time divided by
2.5).