179
High-speed Counters Section 5-1
Conditions for Incrementing/Decrementing the Count
The count is incremented when the direction signal is ON and decre-
mented when it is OFF.
Only up-differentiated pulses (rising edges) can be counted.
Up/Down Mode The up/down mode uses two signals, an increment pulse input and a decre-
ment pulse input.
Conditions for Incrementing/Decrementing the Count
The count is incremented for each increment pulse input and decre-
mented for each decrement pulse input.
Only up-differentiated pulses (rising edges) can be counted.
Increment Mode The increment mode counts single-phase pulse signal inputs. This mode only
increments the count.
Conditions for Incrementing/Decrementing the Count
Direction
signal
Pulse
signal
Count value
L No change
H Increment
H No change
L No change
L Decrement
H No change
H No change
L No change
22 1 1 0 0 7 6876 55 44 33
Increment pulse
Decrement pulse
Decrement
pulse
Increment
pulse
Count value
LDecrement
H Increment
H No change
L No change
L Increment
HDecrement
H No change
L No change
142 151 16
0 9 10876 115 124 133
Pulse
Pulse Count value
Increment
H No change
No change
L No change