Pulse Outputs Section 5-2
CPU Units with 20, 30, 40 or 60 I/O Points
Auxiliary Area Data Allocation
Address Default setting High-speed counter operation settings: Origin
searches
Word Bit
CPU Units
with 60 I/O
Points
CPU Units
with 40 I/O
Points
CPU Units
with 30 I/O
Points
CPU Units
with 20 I/O
Points
Single-phase
(increment pulse
input)
Two-phase
(differential phases
x4, up/down, or
pulse/direction)
Origin searches
enabled for
pulse outputs 0
and 1
CIO 0 00 Normal
input 0
Normal
input 0
Normal
input 0
Normal
input 0
Counter 0,
increment input
Counter 0, A phase,
up, or count input
---
01 Normal
input 1
Normal
input 1
Normal
input 1
Normal
input 1
Counter 1,
increment input
Counter 0, B phase,
down, or direction
input
---
02 Normal
input 2
Normal
input 2
Normal
input 2
Normal
input 2
Counter 2,
increment input
Counter 1, A phase,
up, or count input
---
03 Normal
input 3
Normal
input 3
Normal
input 3
Normal
input 3
Counter 3,
increment input
Counter 1, B phase,
down, or direction
input
---
04 Normal
input 4
Normal
input 4
Normal
input 4
Normal
input 4
Counter 0,
phase-Z reset input
Counter 0, phase-Z
reset input
---
05 Normal
input 5
Normal
input 5
Normal
input 5
Normal
input 5
Counter 1,
phase-Z reset input
Counter 1, phase-Z
reset input
---
06 Normal
input 6
Normal
input 6
Normal
input 6
Normal
input 6
Counter 2,
phase-Z reset input
--- Pulse output 0:
Origin input
signal
07 Normal
input 7
Normal
input 7
Normal
input 7
Normal
input 7
Counter 3,
phase-Z reset input
--- Pulse output 1:
Origin input
signal
08 Normal
input 8
Normal
input 8
Normal
input 8
Normal
input 8
--- --- ---
09 Normal
input 9
Normal
input 9
Normal
input 9
Normal
input 9
--- --- ---
10 Normal
input 10
Normal
input 10
Normal
input 10
Normal
input 10
--- --- Pulse output 0:
Origin proxim-
ity input signal
11 Normal
input 11
Normal
input 11
Normal
input 11
Normal
input 11
--- --- Pulse output 1:
Origin proxim-
ity input signal
CIO 1 00 to
05
Normal
input 12
to 17
Normal
input 12
to 17
Normal
input 12
to 17
--- --- --- ---
06 to
11
Normal
input 18
to 23
Normal
input 18
to 23
--- --- --- --- ---
CIO 2 00 to
11
Normal
input 24
to 35
--- --- --- --- --- ---
Function Pulse output number
01
Pulse output PV storage words
PV range: 8000 0000 to 7FFF FFFF hex
(−2,147,483,648 to 2,147,483,647)
Leftmost 4 digits A277 A279
Rightmost 4 digits A276 A278
Reset Bits
The pulse output PV will be cleared when this bit is
turned from OFF to ON.
0: Not cleared.
1: Clear PV.
A540.00 A541.00