EasyManua.ls Logo

Omron CP1L - Page 261

Omron CP1L
763 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
227
Pulse Outputs Section 5-2
If origin compensation is not being applied, the Positioning Completed Signal
is checked after the Error Counter Reset Output. If origin compensation is
being applied, the Positioning Completed Signal is checked after the compen-
sation operation is completed.
Origin Search Operation
Setting
Select either of the following two reverse modes for the origin search opera-
tion pattern.
Origin Detection Method The origin detection method depends on the Origin Proximity Input Signal set-
tings. Select one of the following three methods in each ports parameters.
Origin Detection Method 0: Origin Proximity Input Signal Reversal
Required
1
1
0
0
Pulse output
Error Counter
Reset Output
Positioning
Completed
Signal
Stop
Time
Setting Description
0: Reversal mode 1 When the limit input signal is received in the origin search
direction, reverse and continue operation.
1: Reversal mode 2 When the limit input signal is received in the origin search
direction, generate an error and stop operation.
Setting Description
0: Origin Proximity Input Signal
reversal required.
Reads the first Origin Input Signal after the Ori-
gin Proximity Input Signal goes
OFFONOFF.
1: Origin Proximity Input Signal
reversal not required.
Reads the first Origin Input Signal after the Ori-
gin Proximity Input Signal goes OFFON.
2: Origin Proximity Input Signal not
used.
Just read the Origin Input Signal without using
the Origin Proximity Input Signal.
1
1
0
0
CCW
CW
Origin Proximity
Input Signal
Origin Input
Signal
Pulse output
Deceleration starts when
Origin Proximity Input
Signal goes OFFON.
After the Origin Proximity Input Signal has gone
from OFFONOFF, the motor is stopped
when the Origin Input Signal goes OFFON.
Initial
speed
Acceleration
High speed for
origin search
Deceler-
ation
Proximity speed for origin search
Start when
ORG(889) is
executed.
Stop