249
Pulse Outputs Section 5-2
The number of pulses cannot be changed.
The frequency can be changed.
The output mode and direction cannot be switched.
(2) SPED(885) (Continuous) to SPED(885) (Continuous)
The frequency can be changed.
The output mode and direction cannot be switched.
(3) SPED(885) (Independent) to ACC(888) (Independent)
The number of pulses cannot be changed.
The frequency can be changed.
The acceleration/deceleration rate can be changed.
The output mode and direction cannot be switched.
(4) ACC(888) (Independent) to ACC(888) (Independent)
or PLS2(887) to ACC(888) (Independent)
The number of pulses cannot be changed.
The frequency can be changed.
The acceleration/deceleration rate can be changed. (The rate can
even be changed during acceleration or deceleration.)
The output mode and direction cannot be switched.
(5) SPED(885) (Continuous) to ACC(888) (Continuous)
or ACC(888) (Continuous) to ACC(888) (Continuous)
The frequency can be changed. (The target frequency can even be
changed during acceleration or deceleration.)
The acceleration/deceleration rate can be changed. (The rate can
even be changed during acceleration or deceleration.)
The output mode and direction cannot be switched.
(6) ACC(888) (Independent) to PLS2(887)
The number of pulses can be changed. (The setting can even be
changed during acceleration or deceleration.)
The frequency can be changed. (The target frequency can even be
changed during acceleration or deceleration.)
The acceleration/deceleration rate can be changed. (The rate can
even be changed during acceleration or deceleration.)
The output mode and direction cannot be switched.
(7) ACC(888) (Continuous) to PLS2(887)
The frequency can be changed. (The target frequency can even be
changed during acceleration or deceleration.)
The acceleration/deceleration rate can be changed. (The rate can
even be changed during acceleration or deceleration.)
The output mode and direction cannot be switched.
(8) PLS2(887) to PLS2(887)
The number of pulses can be changed. (The setting can even be
changed during acceleration or deceleration.)
The frequency can be changed. (The target frequency can even be
changed during acceleration or deceleration.)
The acceleration/deceleration rate can be changed. (The rate can
even be changed during acceleration or deceleration.)
The output mode and direction cannot be switched.