254
Pulse Outputs Section 5-2
Positioning (Trapezoidal Control)
Specifications and
Operation
When the start input (0.00) goes ON, this example program outputs 600,000
pulses from pulse output 0 and turns the motor.
Instructions Used PLS2(887)
Preparation
PLC Setup
There are no settings that need to be made in the PLC Setup.
DM Area Settings PLS2(887) Settings (D00000 to D00007)
Ladder Program
Remarks Absolute pulses can be specified when the origin position has been deter-
mined.
If a target frequency that cannot be reached has been set, the target fre-
quency will be reduced automatically, i.e., triangular control will be per-
formed. In some cases where the acceleration rate is substantially greater
than the deceleration rate, the operation won't be true triangular control.
The motor will be operated at a constant speed for a short time between
the acceleration and deceleration.
100 Hz
Target frequency
50,000 Hz
Starting frequency
Start input (0.00)
Acceleration rate
300 Hz/4 ms
Number of
output pulses
600,000 pulses
Deceleration rate
200 Hz/4 ms
Setting details Address Data
Acceleration rate: 300 Hz/4 ms D0 012C
Deceleration rate: 200 Hz/4 ms D1 00C8
Target frequency: 50,000 Hz D2 C350
D3 0000
Number of output pulses: 600,000 pulses D4 27C0
D5 0009
Starting frequency: 100 Hz D6 0064
D7 0000
@PLS2 (887)
#0000
D0
D6
#0001
END(001)
0.00
Pulse output 1
Start input
Specifies CW/CCW output method,
CW side, and relative pulses
Target frequency, number of
pulses setting
Starting frequency