6
Features and Main Functions Section 1-1
CP1L CPU Units
Note (1) Three Expansion I/O Units connected to a CP-series CPU Unit with 60,
40 or 30 I/O Points.
(2) One Expansion I/O Unit connected to a CP-series CPU Unit with 20 or 14
I/O Points.
Type M CPU Units L CPU Units
Model
CP1L-M60DR-A
CP1L-M60DR-D
CP1L-M60DT-A
CP1L-M60DT-D
CP1L-M60DT1-D
CP1L-M40DR-A
CP1L-M40DR-D
CP1L-M40DT-A
CP1L-M40DT-D
CP1L-M40DT1-D
CP1L-M30DR-A
CP1L-M30DR-D
CP1L-M30DT-A
CP1L-M30DT-D
CP1L-M30DT1-D
CP1L-L20DR-A
CP1L-L20DR-D
CP1L-L20DT-A
CP1L-L20DT-D
CP1L-L20DT1-D
CP1L-J20DR-A
CP1L-J20DR-D
CP1L-J20DT1-D
CP1L-L14DR-A
CP1L-L14DR-D
CP1L-L14DT-A
CP1L-L14DT-D
CP1L-L14DT1-D
CP1L-J14DR-A
CP1L-J14DR-D
CP1L-J14DT1-D
CP1L-L10DR-A
CP1L-L10DR-D
CP1L-L10DT-A
CP1L-L10DT-D
CP1L-L10DT1-D
Power supply Models with AC power (model numbers ending in “-A”):
100 to 240 V AC, 50/60 Hz
Models with DC power (model numbers ending in “-D”):
24 V DC
Program capacity 10K steps 5K steps
J models : 1K steps
Maximum number of
I/O points
180
(See note 1.)
160
(See note 1.)
150
(See note 1.)
60
(See note 2.)
54
(See note 2.)
10
(See note 3.)
Normal
I/O
I/O points 60 40 30 20 14 10
Input points 36 24 18 12 8 6
Input
specifications
24 VDC
Interrupt or
quick-response
inputs
6 max 4 max 2 max
Output points 24 16 12 8 6 4
Output
specifications
Relay outputs: Model numbers with “R” before the final suffix
Transistor outputs, sinking: Model numbers with “T” before the final suffix
Transistor outputs, sourcing:Model numbers with “T1” before the final suffix
High-speed counter inputs 4 counters/2 axes, 100 kHz (single-phase),
100 kHz for up/down pulses or pulse plus direction, 50 kHz for differential phases
J models: 4 counters/2 axes, 20kHz (single-phase),
20kHz for up/down pulses or pulse plus direction, 10kHz for differential phases.
Pulse outputs 2 axes, 100 kHz (transistor outputs)
J models : 2 axes, 20kHz (transistor outputs)