377
Serial Communications Section 6-3
Configuration 1:N Connections between CP1L/CJ1M CPU Units (8 Nodes Maximum)
1:1 Connections between CP1L/CJ1M CPU Units
Specifications
Data Refresh Methods
The following two methods can be used to refresh data.
Complete link method
Polling Unit link method
Complete Link Method The data from all nodes in the Serial PLC Links are reflected in both the Poll-
ing Unit and the Polled Units. (The only exceptions are the address allocated
8 nodes maximum
CP1L CPU Unit (Polling Unit)
RS-422A/485 Option Board
RS-422A/485
Shared data
CP1L CPU Unit
(Polled Unit)
CP1L CPU Unit
(Polled Unit)
CJ1M CPU Unit
(Polled Unit)
CP1L CPU Unit
(Polled Unit)
CP1L CPU Unit
(Polling Unit)
RS-232C or RS-422A/485
Shared data
CP1L CPU Unit
(Polled Unit)
CJ1M CPU Unit
(Polling Unit)
RS-232C or RS-422A/485
Shared data
Item Specifications
Applicable serial
ports
Serial port 1 or 2. Both ports cannot be used for PLC Links at
the same time. If both ports are set for PLC Links (either as
polling node or polled node), a PLC Setup setting error (non-
fatal error) will occur and the PLC Setup Setting Error Flag
(A402.10) will turn ON.
Connection method RS-422A/485 or RS-232C connection via RS-422A/485 or
RS-232C Option Board.
Allocated data area Serial PLC Link Words:
CIO 3100 to CIO 3199 (Up to 10 words can be allocated for
each CPU Unit.)
Number of Units 9 Units max., comprising 1 Polling Unit and 8 Polled Units (A
PT can be placed on the same network in an 1:N NT Link, but
it must be counted as one of the 8 Polled Units.)
Link methods (data
refresh methods)
Complete link method or Polling Unit link method