Auxiliary Area Allocations by Address Appendix D
A26 04 Error Counter
Error Flag 0
This flag turns ON when an error
occurs in the error counter for
inverter positioning 0.
ON: Error
counter error
OFF: No error
--- Cleared When
pulse out-
put to error
counter is
stopped
and abso-
lute value
of error
counter
present
value is
greater
than or
equal to
error
counter
error
detection
value
---
05 Error Counter
Pulse Output
Flag 0
This flag is ON while pulses are
being output to the output counter for
inverter positioning 0.
ON: Pulses
being output
OFF: Pulse
output
stopped
--- Cleared When
pulse out-
put to error
counter 0
is started
---
06 Error Counter
Pulse Output
Acceleration/
Deceleration
Flag 0
This flag is ON while pulse output to
the output counter for inverter posi-
tioning 0 is accelerating or decelerat-
ing.
ON: Pulse
output to the
error counter
is accelerat-
ing or decel-
erating (i.e.,
the fre-
quency is
changing)
OFF: Pulse
output to the
error counter
is constant
--- Cleared When
pulse out-
put fre-
quency to
error
counter is
changed
by ACC or
PLS2
instruction
---
07 Error Counter
Alarm Flag 0
This flag turns ON when an alarm
occurs in the error counter for
inverter positioning 0.
ON: Error
counter alarm
OFF: No error
counter alarm
--- Cleared When
pulse out-
put to error
counter is
stopped
and abso-
lute value
of error
counter
present
value is
greater
than or
equal to
error
counter
alarm
detection
value
---
15 Inverter Posi-
tioning Output
Value Sign
Flag 0
This flag is ON when the inverter
positioning 0 output value is positive
and is OFF when it is negative.
ON: Positive
value
OFF: Nega-
tive value
--- Cleared When
signed out-
put value is
between
0000 0000
and 7FFF
FFFF hex
---
A28
and
A29
--- Present Value
of Pulse Out-
put to Inverter
0, Relative
Value
These words contain the relative
value of the internal pulse output
when pulses are being output to the
error counter for inverter positioning
0.
Data range: 8000 0000 to 7FFF
FFFF hex (2,147,483,648 to
2,147,483,647)
--- --- Cleared Every error
counter 0
cycle
---
Address Name Function Settings Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words Bits