647
Auxiliary Area Allocations by Address Appendix D
A406 All PLC Setup
Error Location
When there is a setting error in the
PLC Setup, the location of that error
is written to A406 in 4-digit hexadeci-
mal.
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
(A406 will be cleared when the
cause of the error is eliminated.)
0000 to 01FF
hexadecimal
Cleared Cleared Refreshed
when error
occurs.
A402.10
A407 A407.00
to
A407.12
Too Many I/O
Points, Details
Always 0000 hex. 0000 hex Cleared Cleared --- A401.11,
A407.13
to
A407.15
A407.13
to
A407.15
Too Many I/O
Points, Cause
The 3-digit binary value of these bits
indicates the cause of the Too Many
I/O Points Error.
Note These bits will be cleared
when the error is cleared.
010: Too
many Expan-
sion Unit and
Expansion I/O
Unit words
011: Too
many Expan-
sion Units
and Expan-
sion I/O Units
Cleared Cleared Refreshed
when error
occurs.
---
A424 A424.00
to
A424.15
Error Option
Board Flags
The bit corresponding to the option
slot turns ON when an error occurs
in an Option Board (A315.13 will be
ON).
Bit 00: Option slot 1
Bit 01: Option slot 2
ON: Error
OFF: No error
Cleared Cleared --- A353.13
A436 A436.00
to
A436.02
CPM1A Unit
Error Flags
ON when an error occurs in a CP-
series Expansion Unit or Expansion
I/O Unit.
A436.00: 1st Unit
A436.10: 2nd Unit
A436.02: 3rd Unit
OFF: No error
ON: Error
Retained Cleared --- ---
A437 All Number of
Connected
CPM1A Units
Stores the number of Expansion
Units and Expansion I/O Units con-
nected as a hexadecimal number.
Note This information is valid only
when a Too Many I/O Points
error has occurred. CP1W/
CPM1A-TS002 and CP1W/
CPM1A-TS102 are each
counted as two Units.
0000 to 0007
hex
Retained Cleared --- ---
A438 All Pulse Output
2 Stop Error
Code
If a Pulse Output Stop Error occurs
for pulse output 2, the error code is
stored.
--- Retained Cleared Refreshed
when ori-
gin search
starts.
Refreshed
when a
pulse out-
put stop
error
occurs.
---
A439 All Pulse Output
3 Stop Error
Code
If a Pulse Output Stop Error occurs
for pulse output 3, the error code is
stored.
--- Retained Cleared Refreshed
when ori-
gin search
starts.
Refreshed
when a
pulse out-
put stop
error
occurs.
---
A440 All Max. Interrupt
Task Process-
ing Time
Contains the Maximum Interrupt
Task Processing Time in units of
0.1 ms.
(This value is written after the inter-
rupt task with the max. processing
time is executed and cleared when
PLC operation begins.)
0000 to FFFF
hexadecimal
Cleared Cleared See Func-
tion col-
umn.
---
Address Name Function Settings Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words Bits