4 Parameter List
4 - 29
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Changes
during
RUN
Unit
Page
Communications
Function
C071
Communication
Speed Selection
(Baud Rate Selec-
tion)
03: 2400 bps
04: 4800 bps
05: 9600 bps
06: 19.2 kbps
07: 38.4 kbps
08: 57.6 kbps
09: 76.8 kbps
10: 115.2 kbps
05
Enabled
P. 8-5
C072
Communication Sta-
tion No. Selection
1. to 247.
1.
Enabled
P. 8-5
C074
Communication Par-
ity Selection
00: No parity
01: Even parity
02: Odd parity
00
Enabled
C075
Communication Stop
Bit Selection
1: 1 bit
2: 2 bits
1
Enabled
C076
Operation Selection
on Communication
Error
00: Trip
01: Trip after deceleration stop
02: Ignore
03: Free-run stop
04: Deceleration stop
02
Enabled
C077
Communication Error
Timeout Time
0.00: Timeout disabled
0.01 to 99.99
0.00
Enabled
s
C078
Communication Wait
Time
0. to 1000.
0.
Enabled
ms
Adjustment
C081
O Adjustment
0.0 to 200.0
100.0
Enabled
%
P. 7-25
C082
OI Adjustment
0.0 to 200.0
100.0
Enabled
%
C085
Thermistor Adjust-
ment
0.0 to 200.0
100.0
Enabled
%
P. 7-82
C091
(Reserved)
Do not change the default 00.
00
Communications
Functions
C096
Communication
Selection
00: Modbus communication
01: Co-inverter communication
02: Co-inverter communication (man-
agement inverter)
00
Enabled
P. 8-31
C098
Co-inverter Commu-
nication Starting Sta-
tion Number
1. to 8.
1.
Disabled
C099
Co-inverter Commu-
nication Ending Sta-
tion Number
1. to 8.
1.
Disabled
C100
Co-inverter Commu-
nication Start Selec-
tion
00: Start via 485 terminal
01: Constant communication
00
Disabled
4
4-3 Extended Function Mode
4-3-3 Group C: Multi-function Terminal Function Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC