424
Note 1. The
area specified under “Name” must be in four characters. Fill any gaps
with spaces to make a total of four characters.
2. Words 253 to 255 cannot be set when the CIO Area is specified.
11-3-26 MULTIPLE FORCED SET/RESET –– FK
Force
sets, force resets, or cancels the status of the bits in one word in the IR,
SR, LR, HR, AR, or TC area.
Command Format
:
@ FK
x
10
0
x 10
1
x 10
3
x 10
2
x 10
1
x 10
0
OP1 OP2 OP3 OP4
↵
15 14 13 12 11 10 1 0
Node no.
Header
code
Name W
ord
address
Forced set/reset/cancel data
Bit
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
x 16
0
TerminatorFCS
Response Format
@ FK
x
10
0
x 10
1
x 16
1
x 16
0
↵:
Node no.
Header
code
TerminatorFCS
End code
Parameters Name, Word address (Command)
In
“Name”, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced
set
or reset.
Specify the name in four characters. In “W
ord address”, specify the
address of the word that is to be forced set or reset.
Name
Classification Word address setting Bit
OP1 OP2 OP3 OP4
C N T (S) Completion Flag (counter)
C N T R Completion Flag (reversible counter)
T T I M Completion Flag (totalizing timer)
(S): Space
Note Words 253 to 255 cannot be set when the CIO Area is specified.
Host Link Commands