Appendix EPC Setup
464
Word(s) DefaultFunctionBit(s)
DM
6654 00 to 07
Start code (RS-232C)
00 to FF (binary)
0000
08 to 15
12 to 15 of DM 6653 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6653 set to 1:
End code (RS-232C)
00 to FF (binary)
Error Settings (DM 6655)
The following settings are effective after transfer to the PC.
DM 6655
00 to 03
Interrupt programming error enable
0: Detect interrupt programming errors
1: Do not detect
Detect
04 to 07
(Multiple action execution error enable
0: Detect multiple action execution
1: Do not detect )
Detect
08 to 1
1 Cycle time monitor enable
0: Detect long cycles as non-fatal errors
1: Do not detect long cycles
Detect
12 to 15
Low battery error enable
0: Detect low battery voltage as non-fatal error
1: Do not detect low batter voltage
Detect