EasyManuals Logo

Oracle Database Appliance X10 User Manual

Oracle Database Appliance X10
171 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #121 background imageLoading...
Page #121 background image
3. Reconnect the "Y" end of the Retimer cable to the Retimer card in PCIe slot 6.
4. Reinstall all NVMe storage drives into the server front panel storage drive cage.
With the drive latch in the open position, slide the drive into the slot until the drive is fully
seated [1] and then close the drive latch to lock the drive in place [2].
5. Return the server to operation.
a. Install the fan tray and fan modules.
See Install the Fan Tray.
b. Install the air baffle.
See Install the Air Baffle.
c. Install the server top cover.
See Install the Server Top Cover.
d. Return the server to the normal rack position.
See Return the Server to the Normal Rack Position.
e. Reconnect the power cords to the power supplies, and power on the server.
See Powering On Oracle Database Appliance.
f. Verify that the power supply AC OK LED is lit.
Chapter 5
Servicing the Disk Backplane (FRU)
5-29

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle Database Appliance X10 and is the answer not in the manual?

Oracle Database Appliance X10 Specifications

General IconGeneral
BrandOracle
ModelDatabase Appliance X10
CategoryStorage
LanguageEnglish

Related product manuals