Supplement to pulse output operation
When outputting pulses with the PLS+SIGN (direction output) method, pulses will be output
approx. 300 μs later after the output of direction signal (SIGN). (The characteristics of a motor
driver are considered.)
Precautions during programming
Set the target value and movement amount to be within the following range.
-8,388,608 to +8,388,607
When using this instruction in combination with other positioning instructions such as F171,
also set the target values for those instructions to be within the above range.
When using this instruction for a purpose for which high accuracy is required, confirm the
operation using a real machine.
When describing the same channel in both the normal program and the interrupt program, be
sure to program not to execute them simultaneously.
Select "Pulse output" for the channel setting corresponding to the system register no. 402.
By performing the rewriting during RUN while outputting pulses, more pulses than the setting
may be output.
For details of the allocations of I/O and flags, refer to “Allocation of Memory Areas”.
REFERENCE
11.2.2 When Using Pulse Output Function (FP-X Compatible Instruction Mode)
7.2 FP-X Compatible Instruction Mode Control Instruction
7-30 WUME-FPXHPOSG-01