AS-i 3.0 EtherNet/IP Gateway with integrated Safety Monitor
Spezifications
Upon locking of the EMERGENCY-OFF switch S2-1, the motor starter is control-
led via the safe AS-interface output of safety monitor SM2-1.
Calculation of the AS-interface-relevant system reaction time:
t
System total b)
= t
R S2-1
+ t
R System
+ t
R A2-1
= 100ms + 40ms + 50ms = 190ms
System configuration - example 2: Calculation of the system reaction time