Manuale d’uso - MCM260X - 19
5.2 Meaning of the status lights (LED)
RUN LED (green)
indicates that the device is on and distinguished the various operating
phases
COM LED (amber) indicates the effective communication of the MCM260X with other devices
MCM260X-1AD .1 .. .16 indicate the status of the outputs Q.1 .. Q.16
MCM260X-2AD .1 .. .16 indicate the status of the inputs I.1 .. I.16
MCM260X-3/4AD
.1 .. .8 indicate the status of the inputs I.1 .. I.8
.1 .. .8 indicate the status of the outputs Q.1 .. Q.8
MCM260X-5AD
AI1 .. AI4 indicate the status of the analog inputs AI1..AI4 (on: active input
working correctly, flashing: input in error, off: input not activate.
AO1 .. AO2 indicates the status of the analog outputs AO1 and AO2 (on: active
output).
MCM260X-9AD
.1 .. .16 indicate the status of the inputs/output I/Q.16
AI1 .. AI4 indicate the status of the analog inputs AI...AI4 (on: active input
working correctly, flashing: input in error, off: input not activate.
AO1 .. AO2 indicates the status of the analog outputs AQ1 and AO2 (on: active
output).
5.3 Changing the configuration parameters from the
terminal
Press Effect Execute
1
One of the buttons
when the display
is on
0000 appears on the display with the
first number flashing, to indicate
that the instrument is waiting for the
entry of the password to access the
parameters.
2
§ or ¶
The flashing number changes and the
next number can now be changed with
|.
Enter the password (default
value
1234)
3
| to confirm the
password
The display shows the name of the first
configuration parameter
4
§ or ¶
The available parameters are scrolled
down
5
|
The display shows the value of the
selected parameter.
6
| + § o ¶
The value of the parameter is increased
or decreased
Enter the new data that will be
saved when releasing the keys.
To change another parameter
go back to point 4
7
§ + ¶
The configuration procedure is left, the
display will turn off.
The configuration is left automatically
after 20 sec from last pressing a key.