Manuale d’uso - MCM260X - 33
89 Max duration rejection of AI1 sampling (Word modbus )
90 Max duration rejection of AI2 sampling (Word modbus )
91 Max duration rejection of AI3 sampling (Word modbus )
92 Max duration rejection of AI4 sampling (Word modbus )
Defines the maximum absolute difference between the current process value and the new
sample, in order to determine if the value should be discarded or accepted as valid
(and therefore considered while calculating the average managed by the parameter “54..57
Input filter”)
0..200 [thents of second], Default: 45
58 AI1and AI2 conversion frequency
(Word modbus )
59 AI3and AI4 conversion frequency (Word modbus )
Conversion frequency of the digital analog converter. Lower frequencies slow down the sampling
but increase the reading precision; on the contrary, higher frequencies increase the sampling
time to the detriment of the reading precision of the analog input.
0 4 Hz
1 6 Hz
2 8 Hz
3 10 Hz
4 12 Hz
5 17 Hz (Default)
6 20 Hz
7 33 Hz
8 39 Hz
9 50 Hz
10 62 Hz
11 123 Hz
12 242 Hz
13 470 Hz
8.3 UNIT C - ANALOG OUTPUTS
60 AO1 output type (Word modbus )
61 AO2 output type (Word modbus )
It selects the operating mode of the analog output.
0 0..10 V (Default)
1 4..20 mA.
62 AO1 output lower limit
(Word modbus )
63 AO2 output lower limit (Word modbus )
Continuous output range lower limit (value associated to 0 V / 4 mA).
-32767..+32767 [digit], Default: 0.
64 AO1 output upper limit
(Word modbus )
65 AO2 output upper limit (Word modbus )
Continuous output range upper limit (value associated to 10 V / 20 mA).
-32767..+32767 [digit], Default: 1000.
66 AO1 output value in error
(Word modbus )
67 AO2 output value in error (Word modbus )
It determines the value of the analog output in case of error or anomaly.
The value must range between the minimum and maximum limits of the output.
-32767..+32767 [digit], Default: 0.
68 Reserved
(Word modbus )
69 Reserved (Word modbus )
70 Reserved (Word modbus )
71 Reserved (Word modbus )