Manuale d’uso - MCM260X - 31
18 Reserved (Word modbus )
19 Reserved (Word modbus )
20 Reserved (Word modbus )
8.2 UNIT B - ANALOG INPUTS
21 AI1 sensor type (Word modbus )
22 AI2 sensor type (Word modbus )
23 AI3 sensor type (Word modbus )
24 AI4 sensor type (Word modbus )
Sensor selection / analog input configuration
0 Disabled (Default).
1 Tc-K -260 °C..1360 °C
2 Tc-S -40 °C..1760 °C
3 Tc-R -40 °C..1760 °C
4 Tc-J -200 °C..1200 °C
5 Tc-T -260 °C..400 °C
6 Tc-E -260 °C..980 °C
7 Tc-N -260 °C..1280 °C
8 Tc-B 100 °C..1820 °C
9 Pt100 -100 °C..600 °C
10 Ni100 -60 °C..180 °C
11 NTC10K -40 °C..125 °C
12 PTC1K -50 °C..150 °C
13 Pt500 -100 °C..600 °C
14 Pt1000 -100 °C..600 °C
15 0..1V
16 0..5V
17 0..10 V
18 0..20 mA
19 4..20 mA
20 0..60 mV
21 Potentiometer (set the value in parameter 34..37)
25 Degree type
(Word modbus )
0 °C Degrees centigrade (Default)
1 °F Degrees Fahrenheit
2 K Kelvin
26 AI1 input lower limit
(Word modbus )
27 AI2 input lower limit (Word modbus )
28 AI3 input lower limit (Word modbus )
29 AI4 input lower limit (Word modbus )
Analog input lower limit only if normalized. E.g.: with input 4..20 mA V this parameter indicates
the value associated to 4 mA
-32767..+32767, Default: 0.
30 AI1 input upper limit
(Word modbus )
31 AI2 input upper limit (Word modbus )
32 AI3 input upper limit (Word modbus )
33 AI4 input upper limit (Word modbus )
Analog input upper limit only if normalized. E.g.: with input 4..20 mA V this parameter indicates
the value associated to 20 mA
-32767..+32767. Default:1000