28 - MCM260X - User manual
34 AI1 potentiometer value (Word modbus )
35 AI2 potentiometer value (Word modbus )
36 AI3 potentiometer value (Word modbus )
37 AI4 potentiometer value (Word modbus )
It selects the value of the potentiometer connected to the analog input
1..150 kohm. Default: 10kohm
38 Liner limit beyond limits AI1
(Word modbus )
39 Liner limit beyond limits AI2 (Word modbus )
40 Liner limit beyond limits AI3 (Word modbus )
41 Liner limit beyond limits AI4 (Word modbus )
In case of linear input, it allows the process to exceed the limits (Par. 26..29 and 30..33).
0 Disabled (Default).
1 Enabled
42 AI1 offset calibration
(Word modbus )
43 AI2 offset calibration (Word modbus )
44 AI3 offset calibration (Word modbus )
45 AI4 offset calibration (Word modbus )
Offset calibration. Value added to or taken from the process displayed (e.g. it normally corrects
the ambient temperature value).
-10000..+10000 [digit] (decimal.degrees for temperature sensors). Default 0.
46 AI1 gain calibration
(Word modbus )
47 AI2 gain calibration (Word modbus )
48 AI3 gain calibration (Word modbus )
49 AI4 gain calibration (Word modbus )
Gain calibration. Value to be multiplied by the process to calibrate on the operating point. E.g.: to
correct the 0..1000°C operating scale that displays 0..1010°C, set the parameter to -1.0
-1000 (100.0%)...+1000 (+100.0%), Default: 0.0.
50 Reserved
(Word modbus )
51 Reserved (Word modbus )
52 Reserved (Word modbus )
53 Reserved (Word modbus )
54 AI1 input filter (Word modbus )
55 AI2 input filter (Word modbus )
56 AI3 input filter (Word modbus )
57 AI4 input filter (Word modbus )
Analog input reading filter: it increases the stability of the value of the analog reading. Indicates
the number of samples to average in the process calculation.
1...50. (Default: 10)
70 Maximum difference for new AI1 sampling
(Word modbus )
71 Maximum difference for new AI2 sampling (Word modbus )
72 Maximum difference for new AI3 sampling (Word modbus )
73 Maximum difference for new AI4 sampling (Word modbus )
Defines the maximum absolute difference between the current process value and the new
sampling to consider this acceptable value (and therefore inserted in the average managed by
the parameter “54..57 Input filter) or discard it.
1..32767 [thents of °C or digit], Default: 30