II
PFC-6006 5403559 REV D 11/17
KEYPAD STEPS PANEL MENU OPTIONS
Setup Phone Lines 1 & 2:
3. Press Enter or "1" – Line1 Setup.
4. Press Enter or "1" – Enable/Disable.
[Line's current status displays.]
Enter "1" to Enable.
-OR-
Enter "2" to Disable or scroll down &
press Enter.
[Line's updated status displays briey.]
5. Scroll to "Line Monitor" and press Enter.
-OR-
Enter "2" Line Monitor.
[Line's current line monitor setting
displays.]
Enter "1" ON or "2" OFF.
6. Scroll to "No. of Rings" and Enter.
-OR-
Enter "3"No. of Rings.
[Line's current no. of rings displays.]
Enter the number of rings that the panel
will wait before answering, if any.
Press Enter.
7. Scroll to "Ans Machine" and Enter.
-OR-
Enter "4"Ans Machine.
[Line's current answering machine
bypass setting displays.]
Enter "1" ON or "2" OFF.
8. Scroll to "Line Prex"and Enter.
-OR-
Enter "5"Line Prex.
[Line's current line prex setting
displays.]
Press up/down arrows to select the
appropriate prex or pause character, if
required at your site.
Press Enter.
9. Scroll to "Dial Tone Det"and Enter.
-OR-
Enter "6" "Dial Tone DET."
[Line's current dial tone setting displays.]
Enter "1" ON or "2" OFF.
[If changes are made, the "Line Enabled - Change Success" message displays;
however, if no changes are made, the "No Changes" message displays.]
1 = Enable/Disable
2 Line Monitor
L1 Monitor: ON
1 = ON
1 = ON
2 = OFF
[Line's updated monitor setting & "Change Success" or "No Changes" displays.]
[Line's updated ans. machine bypass & "Change Success" / "No Changes" displays.]
4 = Ans Machine
5 = Line Prefix
L1 Bypass: OFF
1 = ON
1 = ON
2 = OFF
4 = Ans Machine
5 = Line Prefix
5 =LinePrefix
6 =Dial Tone DET
L1:
__
[Line's updated prex setting & "Change Success" / "No Changes" displays.]
DACT Setup
1 Line1 Setup
Line1 Setup
1 = Enable/Disable
Line1 Enabled
1 = Enable
1 = Enable
2 = Disable
Line's Default = Enabled. (The DACT can access
the telephone line.)
Line Monitor Default = Enabled. (This tells the DACT to monitor the phone line's
voltage; if the line's voltage is not present or low, a "Trouble" error displays.)
[Line's updated no. of rings & "Change Success" or "No Changes"displays.]
L1 = Rings:03
01
2 = Line Monitor
3 = No.of Rings
3 = No.of Rings
4 = Ans Machine
No. of Rings Default = 3 rings. (This tells the DACT to pick up or answer incoming
phone calls after 3 rings. This option is used only if remote programming is required.)
Answering Machine Bypass Default = OFF. (This setting is used or turned "ON" only
if remote programming is required, and the panel shares the phone line with another
device, i.e., FAX machine).
Line Prex Default = None. ((This setting assumes that the DACT can directly access
an outside phone line without dialing an prex (such as an "9") or waiting for the phone
line to connect. Enter a "," (comma) for each 1 second or pause that is required.))
L1 Dial DET: ON
1 = ON
1 = ON
2 = OFF
5 =Line Prefix
6 =Dial Tone DET
Dial Tone Detection Default = ON. (The DACT listens for a phone line's dial tone,
before calling out to the central station.)
[Line's updated dial tone setting & "Change Success" / "No Changes" displays.]