Flow Meter/Encoder Extension Cables
Before starting this test, disconnect the flow meter cable from the flow meter. Hold the flow meter cable so that
the keyway is pointing in the 12 o’clock position as shown below.
FIGURE 2. Flow Meter Extension Cable Pin Diagram
Note: In a non-CAN system if a +5 voltage reading is not present, disconnect the Speed Sensor cable. If
the voltage reading is restored, test the Speed Sensor cable as described in Flow Meter/Encoder
Extension Cables section on page 267.
Testing the Flow Meter/Encoder Cable
1. Press Product Control.
2. Touch the Product Control Settings area.
3. Touch within the Product Control Settings area to display the node settings screen for the selected control
channel.
4. Enter the number ‘1’ in the Meter Cal field and touch OK.
5. Touch the Tally Registers button at the bottom of the screen.
10 o’clock
Power
2 o’clock
Ground
Keyway
6 o’clock
Signal
5 VDC
5 VDC