MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
122 8540780 • 10/07/2020 • Rev.38
english
Manual reset: If selected this enables the request to reset each time the safety pedal is
activated. Otherwise, enabling of the output directly follows the input conditions.
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double transition
from 0 to 1 and then back to 0 is verified.
t = 250ms
t1 > 250ms
t2 = 250ms

WARNING: If the Manual Reset is active, a consecutive Input have to be used. Example:
Input 1 and Input 2 are used for the functional block, then Input 3 have to be used for
the Reset Input.
Output test: This is used to select which test output signals are to be sent to the component
contacts. This additional control permits detection and management of any short-circuits
between the lines. To enable this control, the test output signals must be configured
(amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by pressing and releasing the footswitch to run a complete function
test and enable the output. This test is only requested at machine start-up (when the unit
is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the contacts.
The length of the filter affects the calculation of the unit's total response time.
With Simultaneity (only with Double NC or Double NC-NO Input type): If selected this
activates the test to verify concurrent switching of the signals coming from the external
contacts.
Simultaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in ms) between the switching of two different signals from the external
contacts.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.

Table of Contents

Other manuals for Reer MOSAIC MI8O4C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer MOSAIC MI8O4C and is the answer not in the manual?

Reer MOSAIC MI8O4C Specifications

General IconGeneral
BrandReer
ModelMOSAIC MI8O4C
CategoryController
LanguageEnglish

Related product manuals